Write the thick gauges as 4/0, 3/0, 2/0 and 1/0, or 0000 to 0. Diameters are for solid wire: stranded wire of the same gauge has the same copper but measures thicker.
d = 0.127 mm × 92^((36 − n) / 39) = 0.127 mm × 92^((36 − 12) / 39) = 2.053 mm
A = π / 4 × d² = π / 4 × (2.053 mm)² = 3.309 mm²
Every gauge from 4/0 to 40 AWG, solid annealed copper. Click a gauge to load it above.
| AWG | Diameter (mm) | Diameter (in) | Area (mm²) | Ω/km | Ω/1000 ft | Nearest metric (mm²) | NEC 75 °C (A)* |
|---|---|---|---|---|---|---|---|
| (0000) | 11.684 | 0.4600 | 107 | 0.161 | 0.0490 | 120 | 230 |
| (000) | 10.405 | 0.4096 | 85.0 | 0.203 | 0.0618 | 95 | 200 |
| (00) | 9.266 | 0.3648 | 67.4 | 0.256 | 0.0779 | 70 | 175 |
| 8.251 | 0.3249 | 53.5 | 0.322 | 0.0983 | 50 | 150 | |
| 7.348 | 0.2893 | 42.4 | 0.407 | 0.124 | 50 | 130 | |
| 6.544 | 0.2576 | 33.6 | 0.513 | 0.156 | 35 | 115 | |
| 5.827 | 0.2294 | 26.7 | 0.646 | 0.197 | 25 | 100 | |
| 5.189 | 0.2043 | 21.2 | 0.815 | 0.248 | 25 | 85 | |
| 4.621 | 0.1819 | 16.8 | 1.03 | 0.313 | 16 | — | |
| 4.115 | 0.1620 | 13.3 | 1.30 | 0.395 | 16 | 65 | |
| 3.665 | 0.1443 | 10.5 | 1.63 | 0.498 | 10 | — | |
| 3.264 | 0.1285 | 8.37 | 2.06 | 0.628 | 10 | 50 | |
| 2.906 | 0.1144 | 6.63 | 2.60 | 0.792 | 6 | — | |
| 2.588 | 0.1019 | 5.26 | 3.28 | 0.999 | 6 | 35 | |
| 2.305 | 0.0907 | 4.17 | 4.13 | 1.26 | 4 | — | |
| 2.053 | 0.0808 | 3.31 | 5.21 | 1.59 | 4 | 25 | |
| 1.828 | 0.0720 | 2.62 | 6.57 | 2.00 | 2.5 | — | |
| 1.628 | 0.0641 | 2.08 | 8.29 | 2.53 | 2.5 | 20 | |
| 1.450 | 0.0571 | 1.65 | 10.4 | 3.18 | 1.5 | — | |
| 1.291 | 0.0508 | 1.31 | 13.2 | 4.02 | 1.5 | — | |
| 1.150 | 0.0453 | 1.04 | 16.6 | 5.06 | 1 | — | |
| 1.024 | 0.0403 | 0.823 | 20.9 | 6.38 | 0.75 | — | |
| 0.912 | 0.0359 | 0.653 | 26.4 | 8.05 | 0.75 | — | |
| 0.812 | 0.0320 | 0.518 | 33.3 | 10.2 | 0.5 | — | |
| 0.723 | 0.0285 | 0.410 | 42.0 | 12.8 | 0.5 | — | |
| 0.644 | 0.0253 | 0.326 | 53.0 | 16.1 | — | — | |
| 0.573 | 0.0226 | 0.258 | 66.8 | 20.4 | — | — | |
| 0.511 | 0.0201 | 0.205 | 84.2 | 25.7 | — | — | |
| 0.455 | 0.0179 | 0.162 | 106 | 32.4 | — | — | |
| 0.405 | 0.0159 | 0.129 | 134 | 40.8 | — | — | |
| 0.361 | 0.0142 | 0.102 | 169 | 51.5 | — | — | |
| 0.321 | 0.0126 | 0.0810 | 213 | 64.9 | — | — | |
| 0.286 | 0.0113 | 0.0642 | 268 | 81.8 | — | — | |
| 0.255 | 0.0100 | 0.0509 | 339 | 103 | — | — | |
| 0.227 | 0.0089 | 0.0404 | 427 | 130 | — | — | |
| 0.202 | 0.0080 | 0.0320 | 538 | 164 | — | — | |
| 0.180 | 0.0071 | 0.0254 | 679 | 207 | — | — | |
| 0.160 | 0.0063 | 0.0201 | 856 | 261 | — | — | |
| 0.143 | 0.0056 | 0.0160 | 1079 | 329 | — | — | |
| 0.127 | 0.0050 | 0.0127 | 1361 | 415 | — | — | |
| 0.113 | 0.0045 | 0.0100 | 1716 | 523 | — | — | |
| 0.101 | 0.0040 | 0.00797 | 2164 | 660 | — | — | |
| 0.090 | 0.0035 | 0.00632 | 2729 | 832 | — | — | |
| 0.080 | 0.0031 | 0.00501 | 3441 | 1049 | — | — |
Diameters from ASTM B258, d = 0.127 mm × 92^((36 − n) / 39), with 4/0 counted as n = −3. Resistance for annealed copper at 20 °C (0.017241 Ω·mm²/m, IEC 60028); it rises about 0.4% per °C. Nearest metric is the closest IEC 60228 size by area; there is none below 0.5 mm².
* NEC (NFPA 70) Table 310.16, 75 °C column, copper: US building wire with at most three current-carrying conductors in a raceway or cable at 30 °C ambient. NEC 240.4(D) limits the breaker on 14, 12 and 10 AWG to 15, 20 and 30 A. It does not apply to wiring inside equipment, flex cords or PCBs. Other gauges are blank because the table doesn't list them.
American Wire Gauge is a logarithmic scale defined in ASTM B258. 36 AWG is fixed at 0.005 in (0.127 mm) and 4/0 at 0.46 in, with 39 equal steps between them, so each step multiplies the diameter by the 39th root of 92 (about 1.123):
d = 0.127 mm × 92^((36 − n) / 39) · A = π / 4 × d²
For 12 AWG: d = 0.127 × 92^(24 / 39) = 2.053 mm and A = π / 4 × 2.053² = 3.31 mm². The thick sizes count below zero: 1/0 is n = 0, 2/0 is −1, 3/0 is −2 and 4/0 is −3.
Rules of thumb that fall out of it: three gauges smaller halves the cross-section (and doubles the resistance), six gauges smaller halves the diameter, and ten gauges smaller is a tenth of the area. A bigger number means a thinner wire.
There is no single safe current for a gauge. It depends on the insulation's temperature rating, how many wires are bundled, the air around them and how much voltage drop you can accept. That is why the chart gives one rating only, from a standard, with its conditions: the 75 °C column of NEC Table 310.16 for US building wire. The popular "chassis wiring" tables online don't cite a standard, so they are left out here.
For wiring inside a device, use the maker's rating for that exact wire and check the voltage drop with the resistance column. A 2 m cable of 18 AWG (20.95 Ω/km) carrying 5 A to a motor has 4 m of copper in the loop: 0.004 km × 20.95 Ω/km × 5 A = 0.42 V lost, 3.5% of 12 V. The Ohm's law calculator does the same sum for any length.
A gauge describes the copper cross-section. Stranded wire of a given gauge has about the same copper as the solid wire, split into thinner strands, but the gaps between them make it measure thicker. So calipers on stranded wire overestimate the gauge; count and measure the strands instead.
Strand counts are written as strands / strand size. 16 AWG 26/30 is 26 strands of 30 AWG: 26 × 0.0509 mm² = 1.32 mm², which is 16 AWG. Metric wire is written the same way: 7/0.25 means 7 strands of 0.25 mm, 7 × π / 4 × 0.25² = 0.34 mm², close to 22 AWG.