Back to Tools

AWG to mm² Converter

Convert American Wire Gauge to square millimetres and diameter, or a metric wire size to the nearest AWG, with the full gauge chart and copper resistance.

Type in any field

Write the thick gauges as 4/0, 3/0, 2/0 and 1/0, or 0000 to 0. Diameters are for solid wire: stranded wire of the same gauge has the same copper but measures thicker.

Result

12 AWG area
3.31 mm²
Diameter
2.053 mm

d = 0.127 mm × 92^((36 − n) / 39) = 0.127 mm × 92^((36 − 12) / 39) = 2.053 mm

A = π / 4 × d² = π / 4 × (2.053 mm)² = 3.309 mm²

Diameter
2.053 mm · 0.0808 in
Circular mils
6 530 cmil
Copper resistance at 20 °C
5.211 Ω/km · 1.588 Ω/1000 ft
Nearest metric size (IEC 60228)
4 mm²
Metric size at least as big
4 mm²
US building wire, NEC Table 310.16, 75 °C column: 25 A for copper, at most three current-carrying conductors in a cable or conduit, 30 °C ambient. NEC 240.4(D) still limits the breaker or fuse to 20 A. Not a rating for chassis, hookup or flex wire. A wire carrying more than it is rated for overheats and can start a fire.

AWG wire gauge chart

Every gauge from 4/0 to 40 AWG, solid annealed copper. Click a gauge to load it above.

AWGDiameter (mm)Diameter (in)Area (mm²)Ω/kmΩ/1000 ftNearest metric (mm²)NEC 75 °C (A)*
(0000)11.6840.46001070.1610.0490120230
(000)10.4050.409685.00.2030.061895200
(00)9.2660.364867.40.2560.077970175
8.2510.324953.50.3220.098350150
7.3480.289342.40.4070.12450130
6.5440.257633.60.5130.15635115
5.8270.229426.70.6460.19725100
5.1890.204321.20.8150.2482585
4.6210.181916.81.030.31316—
4.1150.162013.31.300.3951665
3.6650.144310.51.630.49810—
3.2640.12858.372.060.6281050
2.9060.11446.632.600.7926—
2.5880.10195.263.280.999635
2.3050.09074.174.131.264—
2.0530.08083.315.211.59425
1.8280.07202.626.572.002.5—
1.6280.06412.088.292.532.520
1.4500.05711.6510.43.181.5—
1.2910.05081.3113.24.021.5—
1.1500.04531.0416.65.061—
1.0240.04030.82320.96.380.75—
0.9120.03590.65326.48.050.75—
0.8120.03200.51833.310.20.5—
0.7230.02850.41042.012.80.5—
0.6440.02530.32653.016.1——
0.5730.02260.25866.820.4——
0.5110.02010.20584.225.7——
0.4550.01790.16210632.4——
0.4050.01590.12913440.8——
0.3610.01420.10216951.5——
0.3210.01260.081021364.9——
0.2860.01130.064226881.8——
0.2550.01000.0509339103——
0.2270.00890.0404427130——
0.2020.00800.0320538164——
0.1800.00710.0254679207——
0.1600.00630.0201856261——
0.1430.00560.01601079329——
0.1270.00500.01271361415——
0.1130.00450.01001716523——
0.1010.00400.007972164660——
0.0900.00350.006322729832——
0.0800.00310.0050134411049——

Diameters from ASTM B258, d = 0.127 mm × 92^((36 − n) / 39), with 4/0 counted as n = −3. Resistance for annealed copper at 20 °C (0.017241 Ω·mm²/m, IEC 60028); it rises about 0.4% per °C. Nearest metric is the closest IEC 60228 size by area; there is none below 0.5 mm².

* NEC (NFPA 70) Table 310.16, 75 °C column, copper: US building wire with at most three current-carrying conductors in a raceway or cable at 30 °C ambient. NEC 240.4(D) limits the breaker on 14, 12 and 10 AWG to 15, 20 and 30 A. It does not apply to wiring inside equipment, flex cords or PCBs. Other gauges are blank because the table doesn't list them.

How to convert AWG to mm²

American Wire Gauge is a logarithmic scale defined in ASTM B258. 36 AWG is fixed at 0.005 in (0.127 mm) and 4/0 at 0.46 in, with 39 equal steps between them, so each step multiplies the diameter by the 39th root of 92 (about 1.123):

d = 0.127 mm × 92^((36 − n) / 39)  ·  A = π / 4 × d²

For 12 AWG: d = 0.127 × 92^(24 / 39) = 2.053 mm and A = π / 4 × 2.053² = 3.31 mm². The thick sizes count below zero: 1/0 is n = 0, 2/0 is −1, 3/0 is −2 and 4/0 is −3.

Rules of thumb that fall out of it: three gauges smaller halves the cross-section (and doubles the resistance), six gauges smaller halves the diameter, and ten gauges smaller is a tenth of the area. A bigger number means a thinner wire.

Current rating and voltage drop

There is no single safe current for a gauge. It depends on the insulation's temperature rating, how many wires are bundled, the air around them and how much voltage drop you can accept. That is why the chart gives one rating only, from a standard, with its conditions: the 75 °C column of NEC Table 310.16 for US building wire. The popular "chassis wiring" tables online don't cite a standard, so they are left out here.

For wiring inside a device, use the maker's rating for that exact wire and check the voltage drop with the resistance column. A 2 m cable of 18 AWG (20.95 Ω/km) carrying 5 A to a motor has 4 m of copper in the loop: 0.004 km × 20.95 Ω/km × 5 A = 0.42 V lost, 3.5% of 12 V. The Ohm's law calculator does the same sum for any length.

An undersized wire heats up along its whole length and can melt its insulation or start a fire, so size it for the fuse or breaker feeding it, not just the load. Fixed mains wiring has to follow your local electrical code (NEC, IEC 60364, BS 7671), which this converter doesn't replace.

Stranded vs solid wire

A gauge describes the copper cross-section. Stranded wire of a given gauge has about the same copper as the solid wire, split into thinner strands, but the gaps between them make it measure thicker. So calipers on stranded wire overestimate the gauge; count and measure the strands instead.

Strand counts are written as strands / strand size. 16 AWG 26/30 is 26 strands of 30 AWG: 26 × 0.0509 mm² = 1.32 mm², which is 16 AWG. Metric wire is written the same way: 7/0.25 means 7 strands of 0.25 mm, 7 × π / 4 × 0.25² = 0.34 mm², close to 22 AWG.

Questions people ask

What is 12 AWG in mm²?
3.31 mm², 2.05 mm across. The nearest metric size is 4 mm²; 2.5 mm² is noticeably smaller.
What is 14 AWG in mm²?
2.08 mm², 1.63 mm across. The closest metric size is 2.5 mm², and 1.5 mm² is smaller.
What is 16 AWG in mm²?
1.31 mm², 1.29 mm across. The closest metric size is 1.5 mm².
What is 6 AWG in mm²?
13.3 mm², 4.11 mm across. The closest metric size is 16 mm²; 10 mm² is a lot smaller.
Can I swap a metric wire for an AWG one?
Only with one at least as big. Nearest is not always bigger: 18 AWG (0.82 mm²) is nearest to 0.75 mm², which has less copper. The converter shows both the nearest size and the smallest one that is not thinner.
What size do screw terminals take?
Terminal blocks list a range, such as 26–12 AWG or 0.14–2.5 mm², often separately for solid and stranded wire. Fine stranded wire goes in more reliably with a crimped ferrule of the matching size.

Related tools and guides

Describe a circuit. Get a board you can order.

GrandpaCAD's chat picks real parts, draws the schematic, routes the PCB and checks it against JLCPCB's rules. You get Gerbers, BOM, pick-and-place, a KiCad project and a 3D board, plus a printed case if you want one.

"12 V motor driver board with screw terminals for 14 AWG wire"

3 free generations, no card required